Variable refrigerant flow (VRF) and variable air volume (VAV) systems are considered among the best heating, ventilation, and air conditioning systems (HVAC) thanks to their ability to provide cooling and heating in different thermal zones of the same building. As well as their ability to recover the heat rejected from spaces requiring cooling and reuse it to heat another space. Nevertheless, at the same time, these systems are considered one of the most energy-consuming systems in the building. So, it is crucial to well size the system according to the building’s cooling and heating needs and the indoor temperature fluctuations. This study aims to compare these two energy systems by conducting an energy model simulation of a real building under a semi-arid climate for cooling and heating periods. The developed building energy model (BEM) was validated and calibrated using measured and simulated indoor air temperature and energy consumption data. The study aims to evaluate the effect of these HVAC systems on energy consumption and the indoor thermal comfort of the building. The numerical model was based on the Energy Plus simulation engine. The approach used in this paper has allowed us to reach significant quantitative energy saving along with a high level of indoor thermal comfort by using the VRF system compared to the VAV system. The findings prove that the VRF system provides 46.18% of the annual total heating energy savings and 6.14% of the annual cooling and ventilation energy savings compared to the VAV system.
This paper presents a framework for numerical building validation enhancement based on detailed building specifications from in-situ measurements and evidence-based validation assessment undertaken on a detached sustainable lightweight building in a semi-arid climate. The validation process has been undergone in a set of controlled experiments – a free-float period, and steady-state internal temperatures. The validation was conducted for a complete year with a 1-min time step for the hourly indoor temperature and the variable refrigerant flow (VRF) energy consumption. The initial baseline model was improved by three series of validation steps per three different field measurements including thermal transmittance, glazing thermal and optical properties, and airtightness. Then, the accurate and validated model was used for building energy efficiency assessment in 12 regions of Morocco. This study aims to assess the effect of accurate building characteristics values on the numerical model enhancement. The initial CV(RMSE) and NMBE have improved respectively from 14.58 % and −11.23 %–7.85 % and 1.86 % for the indoor temperature. Besides, from 31.17 % to 14.37 %–20.57 % and 9.77 % for energy consumption. The findings demonstrate that the lightweight construction with the use of a variable refrigerant flow system could be energy efficient in the southern regions of Morocco.
The variable refrigerant flow system is one of the best heating, ventilation, and air conditioning systems (HVAC) thanks to its ability to provide thermal comfort inside buildings. But, at the same time, these systems are considered one of the most energy-consuming systems in the building sector. Thus, it is crucial to well size the system according to the building’s cooling and heating needs and the indoor temperature fluctuations. Although many researchers have studied the optimization of the building energy performance considering heating or cooling needs, using air handling units, radiant floor heating, and direct expansion valves, few studies have considered the use of multi-objective optimization using only the thermostat setpoints of VRF systems for both cooling and heating needs. Thus, the main aim of this study is to conduct a sensitivity analysis and a multi-objective optimization strategy for a residential building containing a variable refrigerant flow system, to evaluate the effect of the building performance on energy consumption and improve the building energy efficiency. The numerical model was based on the EnergyPlus, jEPlus, and jEPlus+EA simulation engines. The approach used in this paper has allowed us to reach significant quantitative energy saving by varying the cooling and heating setpoints and scheduling scenarios. It should be stressed that this approach could be applied to several HVAC systems to reduce energy-building consumption.
The contribution of the RoofKIT student team to the SDE 21/22 competition is the extension of an existing café in Wuppertal, Germany, to create new functions and living space for the building with simultaneous energetic upgrading. A demonstration unit is built representing a small cut-out of this extension. The developed energy concept was thoroughly simulated by the student team in seminars using Modelica. The system uses mainly solar energy via PVT collectors as the heat source for a brine-water heat pump (space heating and hot water). Energy storage (thermal and electrical) is installed to decouple generation and consumption. Simulation results confirm that carbon neutrality is achieved for the building operation, consuming and generating around 60 kWh/m2a.
A strong heat load in buildings and cities during the summer is not a new phenomenon. However, prolonged heat waves and increasing urbanization are intensifying the heat island effect in our cities; hence, the heat exposure in residential buildings. The thermophysiological load in the interior and exterior environments can be reduced in the medium and long term, through urban planning and building physics measures. In the short term, an increasingly vulnerable population must be effectively informed of an impending heat wave. Building simulation models can be favorably used to evaluate indoor heat stress. This study presents a generic simulation model, developed from monitoring data in urban multi-unit residential buildings during a summer period and using statistical methods. The model determines both the average room temperature and its deviations and, thus, consists of three sub-models: cool, average, and warm building types. The simulation model is based on the same mathematical algorithm, whereas each building type is described by a specific data set, concerning its building physical parameters and user behavior, respectively. The generic building model may be used in urban climate analyses with many individual buildings distributed across the city or in heat–health warning systems, with different building and user types distributed across a region. An urban climate analysis (with weather data from a database) may evaluate local differences in urban and indoor climate, whereas heat–health warning systems (driven by a weather forecast) obtain additional information on indoor heat stress and its expected deviations.
There is a strong interaction between the urban atmospheric canopy layer and the building energy balance. The urban atmospheric conditions affect the heat transfer through exterior walls, the long-wave heat transfer between the building surfaces and the surroundings, the short-wave solar heat gains, and the heat transport by ventilation. Considering also the internal heat gains and the heat capacity of the building structure, the energy demand for heating and cooling and the indoor thermal environment can be calculated based on the urban microclimatic conditions. According to the building energy concept, the energy demand results in an (anthropogenic) waste heat; this is directly transferred to the urban environment. Furthermore, the indoor temperature is re-coupled via the building envelope to the urban environment and affects indirectly the urban microclimate with a temporally lagged and damped temperature fluctuation. We developed a holistic building model for the combined calculation of indoor climate and energy demand based on an analytic solution of Fourier's equation and implemented this model into the PALM model.
It is considered necessary to implement advanced controllers such as model predictive control (MPC) to utilize the technical flexibility of a building polygeneration system to support the rapidly expanding renewable electricity grid. These can handle multiple inputs and outputs, uncertainties in forecast data, and plant constraints, amongst other features. One of the main issues identified in the literature regarding deploying these controllers is the lack of experimental demonstrations using standard components and communication protocols. In this original work, the economic-MPC-based optimal scheduling of a real-world heat pump-based building energy plant is demonstrated, and its performance is evaluated against two conventional controllers. The demonstration includes the steps to integrate an optimization-based supervisory controller into a typical building automation and control system with off-the-shelf HVAC components and usage of state-of-art algorithms to solve a mixed integer quadratic problem. Technological benefits in terms of fewer constraint violations and a hardware-friendly operation with MPC were identified. Additionally, a strong dependency of the economic benefits on the type of load profile, system design and controller parameters was also identified. Future work for the quantification of these benefits, the application of machine learning algorithms, and the study of forecast deviations is also proposed.
Techno-economic comparison of membrane distillation and MVC in a zero liquid discharge application
(2018)
Membrane distillation (MD) is a thermally driven membrane process for the separation of vapour from a liquid stream through a hydrophobic, microporous membrane. However, a commercial breakthrough on a large scale has not been achieved so far. Specific developments on MD technology are required to adapt the technology for applications in which its properties can potentially outshine state of the art technologies such as standard evaporation. In order to drive these developments in a focused manner, firstly it must be shown that MD can be economically attractive in comparison to state of the art systems. Thus, this work presents a technological design and economic analysis for AGMD and v-AGMD for application in a zero liquid discharge (ZLD) process chain and compares it to the costs of mechanical vapour compression (MVC) for the same application. The results show that MD can potentially be ~40% more cost effective than MVC for a system capacity of 100 m3/day feed water, and up to ~75% more cost effective if the MD is driven with free waste heat.